Protocol Conversion: It enables the communication conversion between the Modbus TCP/IP protocol and the PROFINET protocol, allowing controllers based on Modbus TCP/IP to control PROFINET devices.
Multi-device Control: It can control up to 36 PROFINET RT devices, such as field I/O, drives, human-machine interfaces, and controllers.
Network Isolation: Equipped with two Ethernet ports that are isolated from each other, allowing devices with different protocols to be located in different subnets, which is convenient for network configuration and management.
Remote Configuration and Diagnosis: It supports remote configuration and diagnosis functions. You can remotely view and manage the status of Modbus TCP/IP and PROFINET networks through the network, making maintenance and troubleshooting easier.
Configuration Storage: There is an onboard SD card slot (SD card is optional) for storing configuration files, enabling configuration backup, restoration, and the transfer of configurations between different gateways.
2. Technical Parameters
Modbus TCP/IP Specifications: Supports a variety of Modbus function codes, including reading coil status, input status, holding registers, input registers, forcing a single coil, presetting a single holding register, etc.; supports 10 clients, MBAP supports 5 servers, and encapsulation supports 5 servers; up to 160 client commands can be configured, and each command can be individually enabled or disabled, and writing only when data changes is supported.
PROFINET Specifications: Drive types are Class 1 RTC and Class 1 RTA; PROFINET I/O data is 3840 bytes of input and 3840 bytes of output; supports cyclic real-time (RT) and acyclic data exchange types; can connect up to 36 PROFINET devices, and each device has a maximum data input/output of 1440 bytes.
Hardware Specifications: The power supply is a nominal voltage of 24VDC, with an allowable range of 10-36VDC; the current load is 400mA at a nominal 24VDC, and the maximum is 610mA at 10-36VDC; the operating temperature is 0°C to 50°C, and the storage temperature is -10°C to 70°C; the relative humidity is 5% to 95% without condensation; the size is 14.01cm×5.24cm×11.09cm; the Ethernet ports are 10/100Mbit RJ45 connectors, and the electrical isolation is 1500Vrms at 50 to 60Hz for 60 seconds.
3. Application Scenarios
Automobile Manufacturing Production Lines: In an automobile production workshop, it connects the PLC with the Modbus TCP/IP protocol and the robots, conveyor line motors, and other devices with the PROFINET protocol to achieve efficient collaboration in the automated production process.
Chemical Production Process Control: It is used to connect the Modbus TCP/IP monitoring system in chemical production with the on-site instruments, regulating valves, and other devices of PROFINET to achieve precise production process control and data collection.
Intelligent Building Systems: In intelligent buildings, it connects the central control system with Modbus TCP/IP and the lighting, air conditioning, security, and other subsystems of PROFINET to achieve centralized management and intelligent control of building equipment.