Key Technical Specifications
- Product Model: F3DIO16/801
- Manufacturer: HIMA
- System Platform: HIMatrix F30 / F35 / F60
- Safety Integrity Level: SIL 3 (IEC 61508), Category 4 / PL e (EN ISO 13849-1)
- Number of Channels: 8 safe digital inputs + 8 safe digital outputs (2 groups of 4 DO)
- Input Voltage Range: 18–30 VDC (24 VDC nominal), sensor supply via module
- Input Current: 4.5 mA @ 24 V per channel, short-circuit proof
- Output Type: Solid-state, high-side switches, 24 VDC / 2 A per channel (max 8 A total module)
- Diagnostic Coverage: >99 % (internal cross-monitoring and line monitoring on DI/DO)
- Response Time: ≤ 12 ms (safety reaction time including SafeEthernet)
- Communication Protocol: SafeEthernet (HIMA proprietary safety layer over standard Ethernet)
- Power Consumption: 5.5 W typical
- Operating Temperature: –25 °C to +70 °C (extended range for offshore/marine applications)
- Dimensions (W×H×D): 41 × 130 × 115 mm (single-width HIMatrix module)
- Weight: Approx. 0.45 kg
- Certifications: TÜV SIL3, IEC 61508:2010, IEC 61511, ATEX Zone 2, IECEx, UL/CSA Class I Div 2, marine approvals (DNV-GL, ABS)
- MTBF: > 1,200,000 hours at 40 °C
Technical Architecture & Functional Positioning
The F3DIO16/801 is a core building block of the HIMatrix distributed safety system architecture, positioned at the field I/O layer while maintaining full SIL3 integrity end-to-end without requiring safety relays or external wiring barriers. Each module combines 8 safe inputs and 8 safe outputs in a single 41 mm wide housing, achieving one of the highest channel densities available in certified safety controllers.
Internally, the module uses dual-channel diverse microprocessor architecture with 1oo2D (one-out-of-two with diagnostics) voting and continuous cross-monitoring. Both input and output circuits employ dynamic pulse testing and read-back verification, enabling line monitoring for open-circuit and short-circuit detection without additional test pulses from the field device. This eliminates the classic “test pulse dilemma” that forces many competitors to sacrifice diagnostic coverage to avoid disturbing field devices.
SafeEthernet provides deterministic, TÜV-certified safety communication (black-channel principle per IEC 61784-3) over standard copper or fiber Ethernet infrastructure. The F3DIO16/801 can be located up to 300 m from its parent controller via standard Cat5e cabling while preserving full safety reaction time ≤ 12 ms.
PARKER 3/4″ NPT X 1″ NPT ELBOW FITTINGS, LOT OF 3
PARKER 3/4 MALE NPT X 3/4 MALE NPT FITTINGS, LOT OF 4
PARKER 3/4″ MALE NPT X 3/4″ BULK HEAD FITTING, LOT OF 5
MUELLER B-33752 PRESSURE RELIEF VALVE, LOT OF 2, NIB
FOXBORO 33186 – 1 100mm ROLL CHART LOT OF 3 NIB
FOXBORO 53001-6TX4.5A CHARTS LOT OF 13 NIB
SANKI HD-100MS POWER SOURCE FOR DC MAGNETIC BRAKE NIB
VICKERS 737825 ELEMENT KIT LOT OF 2 NIB
BRISTOL BABCOCK 2218 RECORDING CHART LOT OF 500 NIB
DELTROL 20381-83 PLUG-IN RELAY, LOT OF 6, NIB
I-T-E SN422 60 Amp SAFETY SWITCH
TELCON HT 200 PANEL MOUNTED CURRENT TRANSFORMER LOT 3