Product Core Summary
- Model: F650-B-A-B-F-2-G-0-LO (ordering code F650BABF2G0I)
- Manufacturer: GE Grid Solutions
- Core Function: Economical multifunction feeder management and bay control relay providing full overcurrent, earth-fault, thermal, recloser, and control functions specifically engineered for 24–48 V DC station battery systems
- System Compatibility: Multilin F650 platform, EnerVista software, Modbus RTU, DNP3, IEC 60870-5-103, IEC 61850 via firmware upgrade
- Supply Status: Current production model – factory stock and widely available
- Warranty Standard: 12-month functional warranty, fully tested on GE test platform with 24–48 V DC supply verification
Key Technical Specifications
- Product Model: F650BABF2G0I
- Manufacturer: GE Grid Solutions
- System Platform: Multilin F650 Series
- Front Display: Basic alphanumeric LCD (4 × 20 characters)
- Power Supply: LO range 24–48 V DC (19–56 V DC continuous), 25 VA typical, 100 ms ride-through at 24 V
- Analog Inputs: Phase CTs 5 A nominal (1 A/5 A jumper selectable), neutral 1 A, VT 0–250 V
- Communication: 2 × RS485 rear (Modbus RTU / DNP3 / IEC 60870-5-103), front USB, IRIG-B unmodulated
- I/O Board: Basic “B” – 16 contact inputs (threshold auto-detects 24–48 V DC wet), 8 standard outputs + 4 latching outputs
- Protection Functions: 50P/51P, 50N/51N, 46, 49, 79 (4-shot), 25, 27/59, 81 O/U/R, 50BF, cold-load pickup
- Metering Accuracy: Class 0.5 % current/voltage
- Recording: 479 events @ 1 ms, 32-cycle oscillography
- Operating Temperature: –40 °C to +60 °C (conformal coating optional)
- Certifications & Standards: CE, UL/CSA, IEC 60255, IEEE C37.90, RCM, EAC
Technical Architecture & Functional Positioning
The F650BABF2G0I is identical in protection and control capability to the HI-supply version (F650BABF1G0HIC) but is factory-configured for low-voltage 24–48 V DC station batteries commonly found in telecom sites, older substations, solar farms, and many industrial plants. The LO power supply module includes wider input filtering and higher inrush tolerance to operate reliably on battery-backed DC systems that may experience deep discharge or ripple.
This variant is the standard choice wherever 110–250 V DC is unavailable or where standardization on 48 V DC plant power is required.
GENERAL ELECTRIC SFK1E VARIOUS MOTOR STARTERS LOT OF 2
OMRON G3NA-21OB RELAY NIB
TELEMECANIQUE LA1DN13 RELAY
ELECTROCUBE RG 2409-8 RESISTOR LOT OF 2
GRACO 206 393 MONARCH AIR POWERED PUMP
GRACO 220-563 PRESIDENT AIR POWERED PUMP
GRACO 220-568 PRESIDENT AIR POWERED PUMP
ATLAS COPCO QMM 340 25 4240 0308 80 SERVO MOTOR CONTROL
ATLAS COPCO QMS 340 25 4240 0312 81 SERVO MOTOR CONTROL
ATLAS COPCO QMS 340 25 4240 0312 81 SERVO MOTOR CONTROL
ATLAS COPCO QMM 340 25 4240 0308 80 SERVO MOTOR CONTROL