Sale!

SM811K01 3BSE018173R1 | AC 800M HI Safety Controller Factory Sealed

Original price was: $8,797.00.Current price is: $3,453.00.

Product Core Brief

  • Model: SM811K01 (3BSE018173R1)
  • Brand: ABB
  • Series: AC 800M High Integrity (HI) / System 800xA Safety
  • Core Function: SIL 3 safety CPU module for high-integrity control and monitoring
  • Type: Safety CPU / High Integrity Controller
  • Key Specs: SIL 3 (IEC 61508), 96 MHz MPC862P, 24 V DC, CEX-Bus interconnect
  • Condition: New Original (New Surplus) — not refurbished
Category: SKU: SM811K01 3BSE018173R1 ABB
  • Email:sales@sxrunsheng.cn
  • Phone:+86 15340667322
  • Whatsapp:+86 15340667322
  • Description

    Product Introduction

    Running a safety-critical AC 800M system and need SIL 3 certification? The ABB SM811K01 (3BSE018173R1) is the high-integrity safety CPU that partners with the PM865 processor for 1oo2 diverse architecture safety control.

    This unit delivers 96 MHz processing (MPC862P) with 32 MB SDRAM, executing safety logic in <10 ms cycle times. In field deployments of 800xA HI systems, we’ve seen this module handle ESD, F&G, and turbine protection loops without the latency you get on standard PLCs. CEX-Bus interconnect (via BC810 box) means redundant synchronization with the PM865—if one CPU fails, the other holds the safety state.

    SM811K01 3BSE018173R1 | AC 800M HI Safety Controller Factory Sealed

     

    Installation & Configuration Guide

    Phase 1—Pre-Installation (est. 10 min)
    De-energize the AC 800M rack. Wait 5 minutes for capacitor discharge. Grab a 24 V DC multimeter, ESD wrist strap, and a camera. Export the current safety configuration from Control Builder M. Photograph the existing SM811K01, PM865, BC810 box, and TK852V10 sync cable routing—photo, photo, photo.

    Phase 2—Removal (est. 5 min)
    Label every CEX-Bus cable and sync link before disconnecting. Release the DIN rail latch or backplane locking mechanism. Pull the SM811K01 straight out, perpendicular to the backplane. Inspect the TP868 baseplate connector pins for bent or corroded contacts.

    Phase 3—Installation (est. 10 min)
    Strap on your ESD gear. Verify the part number matches 3BSE018173R1. Seat the SM811K01 onto the TP868 baseplate, ensure the latch clicks. Reconnect the TK852V10 synchronization cable (observe polarity). Reconnect CEX-Bus cables (A to A, B to B). Run a pre-power checklist: supply voltage 24 V DC, ground continuity, no loose strands.

    Phase 4—Power-On & Testing (est. 15 min)
    Apply 24 V DC ±10%. Watch the LEDs: Power = green steady, Run = green flash, Fault = off (red = fault). Connect Control Builder M via Ethernet. Verify the safety configuration downloads without errors. Run a functional test: simulate a safety input (E-stop, F&G alarm), verify safety outputs de-energize within <10 ms, confirm PM865 synchronization (no loss of state). Confirm stable operation for at least 30 minutes. Log the swap in your maintenance record.

    Troubleshooting quick-reference:

    • No power LED → check 24 V DC supply and CEX-Bus polarity
    • Fault LED red → check TK852V10 sync cable, verify PM865 companion status
    • Safety output fails → verify dual-channel input wiring, check SIL 3 configuration in Control Builder M